Product is the clock you are actually racing. The FDA Food Code puts cold holding at 41 F and gives you four hours above it before what is on the shelves is a discard rather than a discussion. Price your own box before you argue with that. Sixty pounds of protein at $6 a pound is $360. Another $400 in dairy, prepped produce and made sauces puts you at $760, and none of that counts the prep labor you cannot re-run or the covers you cannot serve on Friday. Substitute your own numbers and the pattern holds: the box is worth more than the service call. So when the controller reads 48 F, the first move is not to dial anyone. It is to spend ten minutes collecting facts, because a warm box is often something the kitchen can clear itself: a propped door, a fouled condenser or a defrost that has stopped running.
Write down the controller reading. Then take a second reading with an independent probe thermometer placed in the middle of the box at product height, not in the discharge airstream. Sensors sitting in the fan discharge read 6 to 10 degrees colder than the product beside them, and a controller that has drifted 4 degrees will hide a real problem for weeks. Finally, note the time the alarm first tripped.
Those three numbers split the problem in half before anyone opens a panel. A box that crept from 38 F to 47 F across eight hours has a capacity problem: the system is running and losing ground. A box that jumped from 38 F to 52 F in ninety minutes lost refrigeration outright, and something is off, tripped, iced or leaking.
If the coil is iced solid, pull the product to a backup box or a reefer truck now. Ice takes two to six hours to clear and no technician can make that faster.
Not one of these
Enter the ZIP of your premises. You get the businesses whose license covers this trade, nearest first, with the license number and the phone number their register publishes. You call them. We take nothing.
Water on the floor of a walk-in is almost never the box leaking. It is condensate that did not reach the drain, and there are four places it goes wrong. The condensate pan under the evaporator overflows when the drain line is blocked with slime, which happens fastest in a box that runs warm. The drain line freezes inside the box or in the wall, which is what the heat tape inside it exists to prevent, so a failed heat tape reads as a puddle rather than as an electrical fault. The line runs uphill somewhere, usually after somebody moved a shelf onto it. Or the trap outside the box has dried out.
The other pattern is a door problem rather than a drain problem. Warm humid air pouring past a failed gasket condenses on everything cold inside and runs down the walls, and you will see it on the floor near the door rather than under the evaporator. Ice on the door frame or the threshold points the same way.
Check where the water starts before you call. Under the evaporator is a drain job. At the door is a gasket job. Neither is the same visit and neither needs the same parts.
A box that ices over repeatedly is telling you the defrost cycle is not clearing the coil, or that something keeps feeding it humidity faster than defrost can remove it.
Defrost first. Advance the cycle at the controller and watch. A heater that stays cold is an open element or a failed contactor. A cycle that runs and terminates in ninety seconds is a termination sensor calling it done early. A cycle that never starts at all is a timer or a control board. All three present identically from inside the box, as a coil that goes back to ice within a day of being cleared.
Humidity second. Every minute the door is open in summer loads that coil, and so does a gasket that has stopped sealing, a missing strip curtain, or product loaded in warm and still steaming. If the icing started the week somebody stopped using the strip curtain, that is the answer.
Chipping the ice off buys a day and is worth doing to keep trading. It is not the repair, and a box that re-ices after a manual defrost needs the control fault found rather than another manual defrost.
Frost is the cheapest diagnostic on site. Even, light frost across the whole coil face is normal between defrosts. Frost on only the first third of the coil, with bare fins after it, usually means the charge is low, and low charge means a leak somewhere. Heavy ice on the suction line back to the compressor points at a flooding evaporator or a failed expansion valve. Frost on the compressor body itself is a warning: liquid refrigerant is returning to it, and running it in that state is how a $600 repair turns into a $3,200 compressor.
That call takes ninety seconds and changes what the pro puts on the truck. A tech who hears "iced coil, defrost heaters read open" brings heaters and a limit switch. A tech who hears "coil frosted on the inlet third only" brings gauges, a leak detector and a jug of refrigerant. A tech who hears "it is warm" brings a guess.
Every figure below is per part or per task, which is a different thing from the whole-job band on the service page. A diagnostic visit sitting under that band's floor is not a contradiction. For a single walk-in on a standard weekday call, expect $140 to $320 for a diagnostic visit and minor correction: gasket replacement, defrost heater, thermostat, coil clean. Condenser fan motors run $180 to $420 installed. Expansion valves land $320 to $650. A leak search with repair and recharge is $450 to $1,100 depending on how long the search takes, and R-448A or R-449A refrigerant is expensive enough now that a chronic leaker is a business decision, not a maintenance one. Compressor replacement on a small commercial unit is $1,600 to $3,400.
After-hours rates add 1.5x on labor plus a callout of $150 to $300. That premium is worth paying at 6 PM on a Friday with a loaded box, and rarely worth paying for a beer cooler at 11 PM in January.
Track calls per box. Any walk-in that takes three refrigeration visits in twelve months is telling you something, usually that the condensing unit is undersized for a door that now cycles 400 times a day, or that the system is past its useful life at 12 to 15 years. Two sealed-system repairs on the same unit inside two years is a replace signal. Plan that spend in a slow month rather than discovering it on the hottest Saturday of the year.
Where this comes from
Fixadore is one person compiling public license registers. These guides are written from published standards and equipment documentation rather than from site visits, and where a figure comes from a standard the standard is named in the text: the FDA Food Code cold-holding limit, the NFPA 96 hood cleaning intervals, the EPA figure for a running toilet. Nobody has reviewed this page on our behalf, and no business listed on this site was involved in writing it.
Cost figures inside a guide are per part or per task. The band on a service page is per job, so the two do not add up to each other, and a diagnostic visit legitimately costs less than the floor of a whole-job band. Both are our own estimates and neither is a quote from anyone.
Read next
Three minutes on the state's own lookup, what the result does and does not prove, and the two questions to ask on the phone.
· 7 min read
Five checks that take ten minutes, plus the three readings a refrigeration tech needs before loading the truck.
· 7 min read
A spring cooling check and a fall heating check cost $340 to $700, and they are what stand between you and a $9,000 unit replacement.
· 6 min read
Related work
From reading to fixed
Search your ZIP and get the businesses licensed for this work nearest to you, with the number their register publishes.